Dari AVR SX440 SX 440 SX-440 Berlogo STAMFORD - BERGARANSI 3 BULAN 0
Dari AVR SX440 SX 440 SX-440 Berlogo STAMFORD - BERGARANSI 3 BULAN 1
Dari AVR SX440 SX 440 SX-440 Berlogo STAMFORD - BERGARANSI 3 BULAN 2
Dari AVR SX440 SX 440 SX-440 Berlogo STAMFORD - BERGARANSI 3 BULAN 3

AVR SX440 SX 440 SX-440 Berlogo STAMFORD - BERGARANSI 3 BULAN

Pembelian Minimum 1
Negara Asal Taiwan
Update Terakhir 09 Feb 2020
Harga
Rp 2.288.000 *harga belum termasuk PPN

Penjual

Sumber Berkat Abadi

Verified Supplier
Alamat

Jl. Pintu Air 3 No.25-C Pasar Baru - Jakarta Pusat

Detil Produk AVR SX440 SX 440 SX-440 Berlogo STAMFORD - BERGARANSI 3 BULAN

AVR SX440 SX 440 SX-440 Berlogo STAMFORD - BERGARANSI 3 BULANDIJAMIN ANDA PUAS 100%BERGARANSI selama 3 BULANJika Rusak / Tidak Berfungsi maka AVR kami Ganti Baru(Bukan di Repair / diperbaiki, Namun kami GANTI AVR Baru)Garansi Tidak Berlaku, jika :- Salah Pemasangan- Komponen Terbakar-
Dapatkan penawaran terbaik untuk AVR SX440 SX 440 SX-440 Berlogo STAMFORD - BERGARANSI 3 BULAN !
Nama
Jumlah Order
Unit
IndoTrading.com adalah media iklan khusus perusahaan, distributor, Grosir, Agen, Supplier, Trading dan Pabrik. Jika anda tertarik untuk membeli AVR SX440 SX 440 SX-440 Berlogo STAMFORD - BERGARANSI 3 BULAN ini dengan harga murah, Mohon hubungi Kontak Perusahaan ini diatas.

Jika anda adalah perusahaan yang ingin menjual di IndoTrading.com ,
Detil Produk

AVR SX440 SX 440 SX-440 Berlogo STAMFORD - BERGARANSI 3 BULAN

DIJAMIN ANDA PUAS 100%

BERGARANSI selama 3 BULAN

Jika Rusak / Tidak Berfungsi maka AVR kami Ganti Baru
(Bukan di Repair / diperbaiki, Namun kami GANTI AVR Baru)

Garansi Tidak Berlaku, jika :
- Salah Pemasangan
- Komponen Terbakar
- Induksi Petir
- Human Error

Technical specification :

INPUT :
 Voltage 190-264V ac
 Frequency 50-60 Hz nominal
 Phase 1
 Wire 2

OUTPUT :
 Voltage max 90V dc at 207V ac input
 Current continuous 4A dc
 Intermittent 6A for 10 secs
 Resistance 15 ohms minimum

REGULATION
+/- 1% (see note 1)

THERMAL DRIFT
 0.04% per deg. C change in AVR ambient (note 2)

TYPICAL SYSTEM RESPONSE
AVR response 20ms
Filed current to 90% 80 ms
 Machine Volts to 97% 300ms

EXTERNAL VOLTAGE ADJUSTMENT
+/-10% with 1 k ohm 1 watt trimmer (see note 3)

UNDER FREQUENCY PROTECTION
Set point 95% Hz (see note 4)
 Slope 170% down to 30 Hz

UNIT POWER DISSIPATION
12 watts maximum

BUILD UP VOLTAGE
4 Volts @ AVR terminals

ANALOGUE INPUT
Maximum input +/- 5V dc (see note 5)
 Sensitivity 1v for 5% Generator Volts (adjustable)
 Input resistance 1k ohm

QUADRATURE DROOP INPUT
 10 ohms burden
 Max. sensitivity: 0.07 A for 5% droop 0PF
 Max. input: 0.33A

ENVIRONMENTAL
Vibration 20-100 Hz 50mm/sec
 100Hz – 2kHz 3.3g
 Operating temperature -40 to +70 oC
 Relative Humidity 0-70 oC 95% (see note 6)
 Storage temperature -55 to +80 oC

NOTES
1. With 4% engine governing.
2. After 10 minutes.
3. Applies to Mod status S onwards. Generator de-rate
may apply. Check with factory.
4. Factory set, semi-sealed, jumper selectable.
5. Any device connected to the analogue input must be
fully floating (galvanically isolated from ground), with an
insulation strength of 500V ac.
6. Non condensing. 

 

AVR / Automatic Voltage Regulator